เครื่อง VICTRON UPS รุ่น Delta- 31 Series
RECTIFIER
Type : VSI3-120-90
AC input voltage : 400V 3-phase, three wire
AC input voltage range : +15% to -20%
(+15% to -10% if batteries are being charged)
Input frequency : 47-63Hz
Input power required : 12kVA
Inrush current (during 20ms) : 6x Inominal
Output voltage : 135Vdc
Output current limit : 88Adc
Efficiency : 94%
INVERTER
Type : IP1-120/10k
Input voltage range : 100-150Vdc
No-load power consumption : 300Watt
AC output voltage : 230V single phase.
AC output voltage stability, static : 1% over full input voltage, power factor, temperature and load ranges.
AC output voltage stability, dynamic : The mean deviation over one half cycle for 100%
of rated load applied or removed is less than 2%.
Waveform : sinusoidal
Harmonic distortion : 2% max. With linear load over the entire DC input voltage, load and temperature ranges.
Output frequency : 50/60Hz
Output frequency accuracy : 0.01% unless synchronized to the bypass
Power rating
(under normal operating conditions) : 10kVA/8kW
Power factor range : any lagging or leading power factor is permitted within the specified kVA rating.
Efficiency at 20%/50%/100% load
(p.f. = 0.8) : 75/91/90%
Overload behaviour : Essentially constant output voltage up to the peak output rating.
Peak output power : 12kVA during 1 minute.
Short circuit behaviour : The inverter is short circuit proof. The short circuit current is approx. 66A. The static switch will transfer the load to bypass.
Protection : Automatic shut down (or transfer to bypass by static switch, if bypass is present) in case of
- low / high DC voltage
- overtemperature
- overload / short circuit (see above)
Most computers have a switched mode power supply at the input. The input current of a switched mode power supply consists of short pulses with a higher peak value than the equivalent sine wave. For such non-sinusoidal currents the traditional kVA rating of a UPS, defined for a linear load and at 0.8 p.f. lagging, is meaningless. The kVA rating as specified for the Delta series is applicable to linear as well as to non-linear loads, as long as the crest factor remains less than 5:1
BATTERY
1. GENERAL
Technology : sealed lead acid, maintenance free.
Number of ce lls / Nominal voltage : 120 c ells/120Vdc
Float charge level : 135Vdc
Max. charge current : 24Adc
Discharge current : 90Adc
Service life (ambient
temperature 0 ํ C to 30 ํ C : 5 years
2. STANDARD BATTERY
Number of batteries : 20
Nominal capacity (20 hr. rate) : 24Ah (2x12Ah)
Typical autonomy of inverter at
100% / 50% computer load : 10/30 minutes
Total weight of battery system : 90kg
3. LONGER AUTONOMY: BATTERY EXTENSION PACKS
Battery extension packs can be erected nest to the standard DELTA cubicle.
Dimensions of one pack VDA6 : 280x400x790mm
(h x w x d)
Net weight : 30kg
Battery : 120Vdc / 24Ah
Net weight with battery : 120kg
Dimensions of one pack VB1 : 935x400x790mm
(h x w x d)
Net weight : 80kg
Battery : 120Vdc / 24Ah or 72Ah
Net weight with battery : 260kg or 350kg
Battery extension 1 : 120Vdc/12Ah
Total capacity : 36Ah
Typical autonomy, 100/50% load : 15/40 min
No extension packs required,
can be fitted in standard cubicle.
Battery extension 2 : 120Vdc/24Ah
Total capacity : 60Ah
Typical autonomy, 100/50% load : 30/70 m
Packs required : 1 x VDA6
Battery extension 3 : 120Vdc/48Ah
Total capacity : 84Ah
Typical autonomy, 100/50% load : 45/110 m
Packs required : 1 x VB1
Battery extension 4 : 120Vdc/72Ah
Total capacity : 108Ah
Typical autonomy, 100/50% load : 60/130 m
Packs required : 1 x VB1
Longer autonomy : On request.
ยี่ห้อ: | - | รุ่น: | - |
สภาพ: | ใหม่ | ความสมบูรณ์: | 100% |
ราคา: | - | ต้องการ: | ขาย |
เลขบัตรประชาชน: | 310090432XXX | IP Address: | 203.156.92.219 |
ติดต่อ: | สุวิทย์ | อีเมล์: | |
โทรศัพย์: | 02-7526952 | มือถือ: | 0817503837 |
จังหวัด: | กรุงเทพมหานคร | ||
ที่อยู่: | - | ||
คำค้น: | victron | victronมือสอง | ups | victron delta 31 100 | Ups victron delta | |